PVdesignEYA 한국어 Design for free
Solar design guides

Solar DC/AC ratio calculator

The DC/AC ratio (inverter loading ratio) is your total module power divided by your total inverter power. See where your design sits, and how many modules match a target ratio.

Result

Module total (DC)–
Inverter total (AC)–
DC/AC ratio–
Verdict–
Modules for the target ratio–
Per inverter–

The module count is before string sizing. You still need to fit the inverter's MPPT voltage window and string length, so adjust by a module or two.

What the DC/AC ratio means

DC/AC ratio = total module power (kWp) ÷ total inverter rated power (kW)Example: 440 W × 24 = 10.56 kWp on one 8 kW inverter → 1.32

Modules rarely deliver their rated power. Heat, lower sunlight, dirt and wiring losses keep them mostly under 80–90% of rated. So an inverter a bit smaller than the array loses little energy and costs less.

Too high

On clear days around noon the array can produce more than the inverter can pass, and the extra is cut off (clipping). At 1.1–1.3 that loss is often under 1% a year; above 1.5 it can reach several percent. South-facing, steep arrays clip more.

Too low

Below 1.0 the inverter is mostly underused. No energy is lost, but you paid for inverter capacity you do not use, and efficiency at low load is a little lower.

DC/AC ratioWhat it means
Below 1.0Oversized inverter, no clipping
1.1–1.3Most common range, small clipping loss
1.3–1.5Cheaper inverter, check clipping loss
Above 1.5Large clipping, needs an hourly simulation
The real clipping loss depends on the hourly sunlight and temperature at your site. Also check the inverter's maximum DC input power and current.

Size inverters with your real layout

Draw your site on a satellite map. PVdesignEYA places the modules, splits them across inverters and strings, and simulates hourly yield and losses. Free, no install.

Design for free →

FAQ

What is a good DC/AC ratio for solar?

Most systems use 1.1 to 1.3. In that range clipping loss is often under 1% a year while the inverter costs less. Steep south-facing arrays are usually kept toward the lower end.

How many 440 W modules for an 8 kW inverter?

For a 1.2 ratio: 8 kW × 1.2 ÷ 0.44 kW ≈ 22 modules. Then adjust to fit the inverter's string length and MPPT voltage.

Is a DC/AC ratio above 1.5 allowed?

Often yes, if you stay within the inverter's maximum DC input. But clipping loss grows, so check it with an hourly simulation first.